Filtered by vendor Hitachienergy
Subscriptions
Total
94 CVE
CVE | Vendors | Products | Updated | CVSS v3.1 |
---|---|---|---|---|
CVE-2022-3388 | 1 Hitachienergy | 2 Microscada Pro Sys600, Microscada X Sys600 | 2024-11-21 | 8.8 High |
An input validation vulnerability exists in the Monitor Pro interface of MicroSCADA Pro and MicroSCADA X SYS600. An authenticated user can launch an administrator level remote code execution irrespective of the authenticated user's role. | ||||
CVE-2022-2513 | 1 Hitachienergy | 6 650connectivitypackage, 670connectivitypackage, Gms600connectivitypackage and 3 more | 2024-11-21 | 7.1 High |
A vulnerability exists in the Intelligent Electronic Device (IED) Connectivity Package (ConnPack) credential storage function in Hitachi Energy’s PCM600 product included in the versions listed below, where IEDs credentials are stored in a cleartext format in the PCM600 database and logs files. An attacker having get access to the exported backup file can exploit the vulnerability and obtain user credentials of the IEDs. Additionally, an attacker with administrator access to the PCM600 host machine can obtain other user credentials by analyzing database log files. The credentials may be used to perform unauthorized modifications such as loading incorrect configurations, reboot the IEDs or cause a denial-of-service on the IEDs. | ||||
CVE-2022-2277 | 1 Hitachienergy | 2 Microscada X Sys600, Sys600 | 2024-11-21 | 7.5 High |
Improper Input Validation vulnerability exists in the Hitachi Energy MicroSCADA X SYS600's ICCP stack during the ICCP communication establishment causes a denial-of-service when ICCP of SYS600 is request to forward any data item updates with timestamps too distant in the future to any remote ICCP system. By default, ICCP is not configured and not enabled. This issue affects: Hitachi Energy MicroSCADA X SYS600 version 10.2 to version 10.3.1. cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:* | ||||
CVE-2022-2081 | 1 Hitachienergy | 8 Rtu520, Rtu520 Firmware, Rtu530 and 5 more | 2024-11-21 | 7.5 High |
A vulnerability exists in the HCI Modbus TCP function included in the product versions listed above. If the HCI Modbus TCP is enabled and configured, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500 in a high rate, causing the targeted RTU500 CMU to reboot. The vulnerability is caused by a lack of flood control which eventually if exploited causes an internal stack overflow in the HCI Modbus TCP function. | ||||
CVE-2022-29922 | 1 Hitachienergy | 2 Microscada X Sys600, Sys600 | 2024-11-21 | 7.5 High |
Improper Input Validation vulnerability in the handling of a specially crafted IEC 61850 packet with a valid data item but with incorrect data type in the IEC 61850 OPC Server in the Hitachi Energy MicroSCADA X SYS600, MicroSCADA Pro SYS600. The vulnerability may cause a denial-of-service on the IEC 61850 OPC Server part of the SYS600 product. This issue affects: Hitachi Energy MicroSCADA Pro SYS600 version 9.4 FP2 Hotfix 4 and earlier versions Hitachi Energy MicroSCADA X SYS600 version 10 to version 10.3.1. cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.0:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.4:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:* | ||||
CVE-2022-29492 | 1 Hitachienergy | 2 Microscada X Sys600, Sys600 | 2024-11-21 | 5.3 Medium |
Improper Input Validation vulnerability in the handling of a malformed IEC 104 TCP packet in the Hitachi Energy MicroSCADA X SYS600, MicroSCADA Pro SYS600. Upon receiving a malformed IEC 104 TCP packet, the malformed packet is dropped, however the TCP connection is left open. This may cause a denial-of-service if the affected connection is left open. This issue affects: Hitachi Energy MicroSCADA Pro SYS600 version 9.4 FP2 Hotfix 4 and earlier versions Hitachi Energy MicroSCADA X SYS600 version 10 to version 10.3.1. cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.0:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.4:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:* | ||||
CVE-2022-29490 | 1 Hitachienergy | 2 Microscada X Sys600, Sys600 | 2024-11-21 | 8.5 High |
Improper Authorization vulnerability exists in the Workplace X WebUI of the Hitachi Energy MicroSCADA X SYS600 allows an authenticated user to execute any MicroSCADA internal scripts irrespective of the authenticated user's role. This issue affects: Hitachi Energy MicroSCADA X SYS600 version 10 to version 10.3.1. cpe:2.3:a:hitachienergy:microscada_x_sys600:10:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:* | ||||
CVE-2022-28613 | 2 Abb, Hitachienergy | 3 Rtu500 Firmware, Rtu500, Rtu500 Firmware | 2024-11-21 | 7.5 High |
A vulnerability exists in the HCI Modbus TCP function included in the product versions listed above. If the HCI Modbus TCP is en-abled and configured, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the receiving RTU500 CMU to reboot. The vulnerability is caused by the validation error in the length information carried in MBAP header in the HCI Modbus TCP function. | ||||
CVE-2022-1778 | 1 Hitachienergy | 2 Microscada X Sys600, Sys600 | 2024-11-21 | 7.5 High |
Improper Input Validation vulnerability in Hitachi Energy MicroSCADA X SYS600 while reading a specific configuration file causes a buffer-overflow that causes a failure to start the SYS600. The configuration file can only be accessed by an administrator access. This issue affects: Hitachi Energy MicroSCADA X SYS600 version 10 to version 10.3.1. cpe:2.3:a:hitachienergy:microscada_x_sys600:10:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:* | ||||
CVE-2021-40336 | 1 Hitachienergy | 2 Modular Switchgear Monitoring, Modular Switchgear Monitoring Firmware | 2024-11-21 | 5 Medium |
A vulnerability exists in the http web interface where the web interface does not validate data in an HTTP header. This causes a possible HTTP response splitting, which if exploited could lead an attacker to channel down harmful code into the user’s web browser, such as to steal the session cookies. Thus, an attacker who successfully makes an MSM user who has already established a session to MSM web interface clicks a forged link to the MSM web interface, e.g., the link is sent per E-Mail, could trick the user into downloading malicious software onto his computer. This issue affects: Hitachi Energy MSM V2.2 and prior versions. | ||||
CVE-2021-40335 | 1 Hitachienergy | 2 Modular Switchgear Monitoring, Modular Switchgear Monitoring Firmware | 2024-11-21 | 5 Medium |
A vulnerability exists in the HTTP web interface where the web interface does not sufficiently verify if a well-formed, valid, consistent request was intentionally provided by the user who submitted the request. This cause a Cross Site Request Forgery (CSRF), which if exploited could lead an attacker to gain unauthorized access to the web application and perform an unwanted operation on it without the knowledge of the legitimate user. An attacker, who successfully makes an MSM user who has already established a session to MSM web interface clicks a forged link to the MSM web interface, e.g., link is sent per E-Mail, could perform harmful command on MSM through its web server interface. This issue affects: Hitachi Energy MSM V2.2 and prior versions. | ||||
CVE-2021-40334 | 1 Hitachienergy | 4 Fox615, Fox615 Firmware, Xcm20 and 1 more | 2024-11-21 | 8.6 High |
Missing Handler vulnerability in the proprietary management protocol (port TCP 5558) of Hitachi Energy FOX61x, XCM20 allows an attacker that exploits the vulnerability by activating SSH on port TCP 5558 to cause disruption to the NMS and NE communication. This issue affects: Hitachi Energy FOX61x versions prior to R15A. Hitachi Energy XCM20 versions prior to R15A. | ||||
CVE-2021-40333 | 1 Hitachienergy | 4 Fox615, Fox615 Firmware, Xcm20 and 1 more | 2024-11-21 | 9 Critical |
Weak Password Requirements vulnerability in Hitachi Energy FOX61x, XCM20 allows an attacker to gain unauthorized access to the Data Communication Network (DCN) routing configuration. This issue affects: Hitachi Energy FOX61x versions prior to R15A. Hitachi Energy XCM20 versions prior to R15A. | ||||
CVE-2021-35535 | 1 Hitachienergy | 6 Relion 650, Relion 650 Firmware, Relion 670 and 3 more | 2024-11-21 | 8.1 High |
Insecure Boot Image vulnerability in Hitachi Energy Relion Relion 670/650/SAM600-IO series allows an attacker who manages to get access to the front network port and to cause a reboot sequences of the device may exploit the vulnerability, where there is a tiny time gap during the booting process where an older version of VxWorks is loaded prior to application firmware booting, could exploit the vulnerability in the older version of VxWorks and cause a denial-of-service on the product. This issue affects: Hitachi Energy Relion 670 Series 2.2.2 all revisions; 2.2.3 versions prior to 2.2.3.3. Hitachi Energy Relion 670/650 Series 2.2.0 all revisions; 2.2.4 all revisions. Hitachi Energy Relion 670/650/SAM600-IO 2.2.1 all revisions. | ||||
CVE-2021-35534 | 1 Hitachienergy | 10 Gms600, Gms600 Firmware, Pwc600 and 7 more | 2024-11-21 | 7.2 High |
Insufficient security control vulnerability in internal database access mechanism of Hitachi Energy Relion 670/650/SAM600-IO, Relion 650, GMS600, PWC600 allows attacker who successfully exploited this vulnerability, of which the product does not sufficiently restrict access to an internal database tables, could allow anybody with user credentials to bypass security controls that is enforced by the product. Consequently, exploitation may lead to unauthorized modifications on data/firmware, and/or to permanently disabling the product. This issue affects: Hitachi Energy Relion 670 Series 2.0 all revisions; 2.2.2 all revisions; 2.2.3 versions prior to 2.2.3.5. Hitachi Energy Relion 670/650 Series 2.1 all revisions. 2.2.0 all revisions; 2.2.4 all revisions; Hitachi Energy Relion 670/650/SAM600-IO 2.2.1 all revisions; 2.2.5 versions prior to 2.2.5.2. Hitachi Energy Relion 650 1.0 all revisions. 1.1 all revisions; 1.2 all revisions; 1.3 versions prior to 1.3.0.8; Hitachi Energy GMS600 1.3.0; 1.3.0.1; 1.2.0. Hitachi Energy PWC600 1.0.1 version 1.0.1.4 and prior versions; 1.1.0 version 1.1.0.1 and prior versions. | ||||
CVE-2021-35533 | 1 Hitachienergy | 2 Rtu500, Rtu500 Firmware | 2024-11-21 | 7.5 High |
Improper Input Validation vulnerability in the APDU parser in the Bidirectional Communication Interface (BCI) IEC 60870-5-104 function of Hitachi Energy RTU500 series allows an attacker to cause the receiving RTU500 CMU of which the BCI is enabled to reboot when receiving a specially crafted message. By default, BCI IEC 60870-5-104 function is disabled (not configured). This issue affects: Hitachi Energy RTU500 series CMU Firmware version 12.0.* (all versions); CMU Firmware version 12.2.* (all versions); CMU Firmware version 12.4.* (all versions). | ||||
CVE-2021-35532 | 1 Hitachienergy | 2 Txpert Hub Coretec 4, Txpert Hub Coretec 4 Firmware | 2024-11-21 | 6.7 Medium |
A vulnerability exists in the file upload validation part of Hitachi Energy TXpert Hub CoreTec 4 product. The vulnerability allows an attacker or malicious agent who manages to gain access to the system and obtain an account with sufficient privilege to upload a malicious firmware to the product. This issue affects: Hitachi Energy TXpert Hub CoreTec 4 version 2.0.0; 2.0.1; 2.1.0; 2.1.1; 2.1.2; 2.1.3; 2.2.0; 2.2.1. | ||||
CVE-2021-35531 | 1 Hitachienergy | 2 Txpert Hub Coretec 4, Txpert Hub Coretec 4 Firmware | 2024-11-21 | 6.7 Medium |
Improper Input Validation vulnerability in a particular configuration setting field of Hitachi Energy TXpert Hub CoreTec 4 product, allows an attacker with access to an authorized user with ADMIN or ENGINEER role rights to inject an OS command that is executed by the system. This issue affects: Hitachi Energy TXpert Hub CoreTec 4 version 2.0.0; 2.0.1; 2.1.0; 2.1.1; 2.1.2; 2.1.3; 2.2.0; 2.2.1. | ||||
CVE-2021-35530 | 1 Hitachienergy | 2 Txpert Hub Coretec 4, Txpert Hub Coretec 4 Firmware | 2024-11-21 | 6 Medium |
A vulnerability in the application authentication and authorization mechanism in Hitachi Energy's TXpert Hub CoreTec 4, that depends on a token validation of the session identifier, allows an unauthorized modified message to be executed in the server enabling an unauthorized actor to change an existing user password, and further gain authorized access into the system via login mechanism. This issue affects: Hitachi Energy TXpert Hub CoreTec 4 version 2.0.0 2.1.0; 2.1.0; 2.1.1; 2.1.2; 2.1.3; 2.2.0; 2.2.1. | ||||
CVE-2021-35529 | 1 Hitachienergy | 2 Counterparty Settlement And Billing, Retail Operations | 2024-11-21 | 7.7 High |
Insufficiently Protected Credentials vulnerability in client environment of Hitachi ABB Power Grids Retail Operations and Counterparty Settlement Billing (CSB) allows an attacker or unauthorized user to access database credentials, shut down the product and access or alter. This issue affects: Hitachi ABB Power Grids Retail Operations version 5.7.2 and prior versions. Hitachi ABB Power Grids Counterparty Settlement Billing (CSB) version 5.7.2 and prior versions. |