The Emerson ROC and FloBoss RTU product lines through 2022-05-02 perform insecure filesystem operations. They utilize the ROC protocol (4000/TCP, 5000/TCP) for communications between a master terminal and RTUs. Opcode 203 of this protocol allows a master terminal to transfer files to and from the flash filesystem and carrying out arbitrary file and directory read, write, and delete operations.
Metrics
Affected Vendors & Products
References
History
No history.

Status: PUBLISHED
Assigner: mitre
Published:
Updated: 2024-08-03T06:40:47.846Z
Reserved: 2022-05-04T00:00:00
Link: CVE-2022-30264

No data.

Status : Modified
Published: 2022-08-16T13:15:11.220
Modified: 2024-11-21T07:02:27.773
Link: CVE-2022-30264

No data.