Search Results (16 CVEs found)

CVE Vendors Products Updated CVSS v3.1
CVE-2021-30187 2 Codesys, Wago 55 Runtime Toolkit, 750-8202, 750-8202 Firmware and 52 more 2025-08-15 5.3 Medium
CODESYS V2 runtime system SP before 2.4.7.55 has Improper Neutralization of Special Elements used in an OS Command.
CVE-2021-30195 2 Codesys, Wago 56 Plcwinnt, Runtime Toolkit, 750-8202 and 53 more 2025-08-15 7.5 High
CODESYS V2 runtime system before 2.4.7.55 has Improper Input Validation.
CVE-2021-34583 2 Codesys, Wago 55 Codesys, 750-8202, 750-8202 Firmware and 52 more 2025-08-15 7.5 High
Crafted web server requests may cause a heap-based buffer overflow and could therefore trigger a denial-of- service condition due to a crash in the CODESYS V2 web server prior to V1.1.9.22.
CVE-2021-34584 2 Codesys, Wago 55 Codesys, 750-8202, 750-8202 Firmware and 52 more 2025-08-15 9.1 Critical
Crafted web server requests can be utilised to read partial stack or heap memory or may trigger a denial-of- service condition due to a crash in the CODESYS V2 web server prior to V1.1.9.22.
CVE-2021-34585 2 Codesys, Wago 55 Codesys, 750-8202, 750-8202 Firmware and 52 more 2025-08-15 7.5 High
In the CODESYS V2 web server prior to V1.1.9.22 crafted web server requests can trigger a parser error. Since the parser result is not checked under all conditions, a pointer dereference with an invalid address can occur. This leads to a denial of service situation.
CVE-2021-34586 2 Codesys, Wago 55 Codesys, 750-8202, 750-8202 Firmware and 52 more 2025-08-15 7.5 High
In the CODESYS V2 web server prior to V1.1.9.22 crafted web server requests may cause a Null pointer dereference in the CODESYS web server and may result in a denial-of-service condition.
CVE-2021-34593 2 Codesys, Wago 28 Plcwinnt, Runtime Toolkit, 750-8202 and 25 more 2025-08-15 7.5 High
In CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56 unauthenticated crafted invalid requests may result in several denial-of-service conditions. Running PLC programs may be stopped, memory may be leaked, or further communication clients may be blocked from accessing the PLC.
CVE-2021-34595 2 Codesys, Wago 57 Codesys, Plcwinnt, Runtime Toolkit and 54 more 2025-08-15 8.1 High
A crafted request with invalid offsets may cause an out-of-bounds read or write access in CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56, resulting in a denial-of-service condition or local memory overwrite.
CVE-2021-34596 2 Codesys, Wago 57 Codesys, Plcwinnt, Runtime Toolkit and 54 more 2025-08-15 6.5 Medium
A crafted request may cause a read access to an uninitialized pointer in CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56, resulting in a denial-of-service condition.
CVE-2021-21000 1 Wago 54 750-8202, 750-8202 Firmware, 750-8203 and 51 more 2025-08-15 5.3 Medium
On WAGO PFC200 devices in different firmware versions with special crafted packets an attacker with network access to the device could cause a denial of service for the login service of the runtime.
CVE-2021-21001 1 Wago 54 750-8202, 750-8202 Firmware, 750-8203 and 51 more 2025-08-15 9.1 Critical
On WAGO PFC200 devices in different firmware versions with special crafted packets an authorised attacker with network access to the device can access the file system with higher privileges.
CVE-2021-30186 2 Codesys, Wago 56 Plcwinnt, Runtime Toolkit, 750-8202 and 53 more 2025-08-15 7.5 High
CODESYS V2 runtime system SP before 2.4.7.55 has a Heap-based Buffer Overflow.
CVE-2020-12069 4 Codesys, Festo, Pilz and 1 more 114 Control For Beaglebone, Control For Empc-a\/imx6, Control For Iot2000 and 111 more 2025-05-05 7.8 High
In CODESYS V3 products in all versions prior V3.5.16.0 containing the CmpUserMgr, the CODESYS Control runtime system stores the online communication passwords using a weak hashing algorithm. This can be used by a local attacker with low privileges to gain full control of the device.
CVE-2023-1620 1 Wago 152 750-331, 750-331 Firmware, 750-8202 and 149 more 2024-11-21 4.9 Medium
Multiple WAGO devices in multiple versions may allow an authenticated remote attacker with high privileges to DoS the device by sending a specifically crafted packet to the CODESYS V2 runtime.
CVE-2023-1619 1 Wago 152 750-331, 750-331 Firmware, 750-8202 and 149 more 2024-11-21 4.9 Medium
Multiple WAGO devices in multiple versions may allow an authenticated remote attacker with high privileges to DoS the device by sending a malformed packet.
CVE-2018-5459 1 Wago 19 750-8202, 750-8202\/025-000, 750-8202\/025-001 and 16 more 2024-11-21 N/A
An Improper Authentication issue was discovered in WAGO PFC200 Series 3S CoDeSys Runtime versions 2.3.X and 2.4.X. An attacker can execute different unauthenticated remote operations because of the CoDeSys Runtime application, which is available via network by default on Port 2455. An attacker could execute some unauthenticated commands such as reading, writing, or deleting arbitrary files, or manipulate the PLC application during runtime by sending specially-crafted TCP packets to Port 2455.