Filtered by vendor Siemens
Subscriptions
Total
1930 CVE
CVE | Vendors | Products | Updated | CVSS v3.1 |
---|---|---|---|---|
CVE-2019-18295 | 1 Siemens | 1 Sppa-t3000 Ms3000 Migration Server | 2024-11-21 | 9.8 Critical |
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could trigger a Denial-of-Service condition and potentially gain remote code execution by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18289, CVE-2019-18293, and CVE-2019-18296. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known. | ||||
CVE-2019-18294 | 1 Siemens | 1 Sppa-t3000 Ms3000 Migration Server | 2024-11-21 | 7.5 High |
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18291, CVE-2019-18292, CVE-2019-18298, CVE-2019-18299, CVE-2019-18300, CVE-2019-18301, CVE-2019-18302, CVE-2019-18303, CVE-2019-18304, CVE-2019-18305, CVE-2019-18306, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known. | ||||
CVE-2019-18293 | 1 Siemens | 1 Sppa-t3000 Ms3000 Migration Server | 2024-11-21 | 9.8 Critical |
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could trigger a Denial-of-Service condition and potentially gain remote code execution by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18289, CVE-2019-18295, and CVE-2019-18296. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known. | ||||
CVE-2019-18292 | 1 Siemens | 1 Sppa-t3000 Ms3000 Migration Server | 2024-11-21 | 7.5 High |
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18291, CVE-2019-18294, CVE-2019-18298, CVE-2019-18299, CVE-2019-18300, CVE-2019-18301, CVE-2019-18302, CVE-2019-18303, CVE-2019-18304, CVE-2019-18305, CVE-2019-18306, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known. | ||||
CVE-2019-18291 | 1 Siemens | 1 Sppa-t3000 Ms3000 Migration Server | 2024-11-21 | 7.5 High |
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18292, CVE-2019-18294, CVE-2019-18298, CVE-2019-18299, CVE-2019-18300, CVE-2019-18301, CVE-2019-18302, CVE-2019-18303, CVE-2019-18304, CVE-2019-18305, CVE-2019-18306, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known. | ||||
CVE-2019-18290 | 1 Siemens | 1 Sppa-t3000 Ms3000 Migration Server | 2024-11-21 | 7.5 High |
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18291, CVE-2019-18292, CVE-2019-18294, CVE-2019-18298, CVE-2019-18299, CVE-2019-18300, CVE-2019-18301, CVE-2019-18302, CVE-2019-18303, CVE-2019-18304, CVE-2019-18305, CVE-2019-18306, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known. | ||||
CVE-2019-18289 | 1 Siemens | 1 Sppa-t3000 Ms3000 Migration Server | 2024-11-21 | 9.8 Critical |
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could trigger a Denial-of-Service condition and potentially gain remote code execution by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18293, CVE-2019-18295, and CVE-2019-18296. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known. | ||||
CVE-2019-18288 | 1 Siemens | 1 Sppa-t3000 Application Server | 2024-11-21 | 8.8 High |
A vulnerability has been identified in SPPA-T3000 Application Server (All versions < Service Pack R8.2 SP2). An attacker with valid authentication at the RMI interface could be able to gain remote code execution through an unsecured file upload. Please note that an attacker needs to have access to the Application Highway in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known. | ||||
CVE-2019-18287 | 1 Siemens | 1 Sppa-t3000 Application Server | 2024-11-21 | 5.3 Medium |
A vulnerability has been identified in SPPA-T3000 Application Server (All versions < Service Pack R8.2 SP2). The Application Server exposes directory listings and files containing sensitive information. This vulnerability is independent from CVE-2019-18286. Please note that an attacker needs to have access to the Application Highway in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known. | ||||
CVE-2019-18286 | 1 Siemens | 1 Sppa-t3000 Application Server | 2024-11-21 | 5.3 Medium |
A vulnerability has been identified in SPPA-T3000 Application Server (All versions < Service Pack R8.2 SP2). The Application Server exposes directory listings and files containing sensitive information. This vulnerability is independent from CVE-2019-18287. Please note that an attacker needs to have access to the Application Highway in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known. | ||||
CVE-2019-18285 | 1 Siemens | 1 Sppa-t3000 Application Server | 2024-11-21 | 5.9 Medium |
A vulnerability has been identified in SPPA-T3000 Application Server (All versions < Service Pack R8.2 SP2). The RMI communication between the client and the Application Server is unencrypted. An attacker with access to the communication channel can read credentials of a valid user. Please note that an attacker needs to have access to the Application Highway in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known. | ||||
CVE-2019-18284 | 1 Siemens | 1 Sppa-t3000 Application Server | 2024-11-21 | 9.8 Critical |
A vulnerability has been identified in SPPA-T3000 Application Server (All versions < Service Pack R8.2 SP2). The AdminService is available without authentication on the Application Server. An attacker can use methods exposed via this interface to receive password hashes of other users and to change user passwords. Please note that an attacker needs to have access to the Application Highway in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known. | ||||
CVE-2019-18283 | 1 Siemens | 1 Sppa-t3000 Application Server | 2024-11-21 | 9.8 Critical |
A vulnerability has been identified in SPPA-T3000 Application Server (All versions < Service Pack R8.2 SP2). The AdminService is available without authentication on the Application Server. An attacker can gain remote code execution by sending specifically crafted objects to one of its functions. Please note that an attacker needs to have access to the Application Highway in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known. | ||||
CVE-2019-17007 | 3 Mozilla, Redhat, Siemens | 19 Network Security Services, Enterprise Linux, Rhel Eus and 16 more | 2024-11-21 | 7.5 High |
In Network Security Services before 3.44, a malformed Netscape Certificate Sequence can cause NSS to crash, resulting in a denial of service. | ||||
CVE-2019-17006 | 4 Mozilla, Netapp, Redhat and 1 more | 27 Network Security Services, Hci Compute Node, Hci Management Node and 24 more | 2024-11-21 | 9.8 Critical |
In Network Security Services (NSS) before 3.46, several cryptographic primitives had missing length checks. In cases where the application calling the library did not perform a sanity check on the inputs it could result in a crash due to a buffer overflow. | ||||
CVE-2019-16905 | 3 Netapp, Openbsd, Siemens | 7 Cloud Backup, Steelstore Cloud Integrated Storage, Openssh and 4 more | 2024-11-21 | 7.8 High |
OpenSSH 7.7 through 7.9 and 8.x before 8.1, when compiled with an experimental key type, has a pre-authentication integer overflow if a client or server is configured to use a crafted XMSS key. This leads to memory corruption and local code execution because of an error in the XMSS key parsing algorithm. NOTE: the XMSS implementation is considered experimental in all released OpenSSH versions, and there is no supported way to enable it when building portable OpenSSH. | ||||
CVE-2019-15681 | 4 Canonical, Debian, Libvnc Project and 1 more | 15 Ubuntu Linux, Debian Linux, Libvncserver and 12 more | 2024-11-21 | 7.5 High |
LibVNC commit before d01e1bb4246323ba6fcee3b82ef1faa9b1dac82a contains a memory leak (CWE-655) in VNC server code, which allow an attacker to read stack memory and can be abused for information disclosure. Combined with another vulnerability, it can be used to leak stack memory and bypass ASLR. This attack appear to be exploitable via network connectivity. These vulnerabilities have been fixed in commit d01e1bb4246323ba6fcee3b82ef1faa9b1dac82a. | ||||
CVE-2019-13947 | 1 Siemens | 2 Sinvr 3 Central Control Server, Sinvr 3 Video Server | 2024-11-21 | 4.9 Medium |
A vulnerability has been identified in Control Center Server (CCS) (All versions < V1.5.0). The user configuration menu in the web interface of the Control Center Server (CCS) transfers user passwords in clear to the client (browser). An attacker with administrative privileges for the web interface could be able to read (and not only reset) passwords of other CCS users. | ||||
CVE-2019-13946 | 1 Siemens | 101 Dk Standard Ethernet Controller, Ek-ertec 200, Ek-ertec 200 Firmware and 98 more | 2024-11-21 | 7.5 High |
Profinet-IO (PNIO) stack versions prior V06.00 do not properly limit internal resource allocation when multiple legitimate diagnostic package requests are sent to the DCE-RPC interface. This could lead to a denial of service condition due to lack of memory for devices that include a vulnerable version of the stack. The security vulnerability could be exploited by an attacker with network access to an affected device. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise the availability of the device. | ||||
CVE-2019-13945 | 1 Siemens | 32 S7-200 Smart, S7-200 Smart Firmware, Simatic S7-1200 and 29 more | 2024-11-21 | 6.8 Medium |
A vulnerability has been identified in SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-1200 CPU family < V4.x (incl. SIPLUS variants) (All versions), SIMATIC S7-1200 CPU family V4.x (incl. SIPLUS variants) (All versions with Function State (FS) < 11), SIMATIC S7-200 SMART CPU CR20s (6ES7 288-1CR20-0AA1) (All versions <= V2.3.0 and Function State (FS) <= 3), SIMATIC S7-200 SMART CPU CR30s (6ES7 288-1CR30-0AA1) (All versions <= V2.3.0 and Function State (FS) <= 3), SIMATIC S7-200 SMART CPU CR40 (6ES7 288-1CR40-0AA0) (All versions <= V2.2.2 and Function State (FS) <= 8), SIMATIC S7-200 SMART CPU CR40s (6ES7 288-1CR40-0AA1) (All versions <= V2.3.0 and Function State (FS) <= 3), SIMATIC S7-200 SMART CPU CR60 (6ES7 288-1CR60-0AA0) (All versions <= V2.2.2 and Function State (FS) <= 10), SIMATIC S7-200 SMART CPU CR60s (6ES7 288-1CR60-0AA1) (All versions <= V2.3.0 and Function State (FS) <= 3), SIMATIC S7-200 SMART CPU SR20 (6ES7 288-1SR20-0AA0) (All versions <= V2.5.0 and Function State (FS) <= 11), SIMATIC S7-200 SMART CPU SR30 (6ES7 288-1SR30-0AA0) (All versions <= V2.5.0 and Function State (FS) <= 10), SIMATIC S7-200 SMART CPU SR40 (6ES7 288-1SR40-0AA0) (All versions <= V2.5.0 and Function State (FS) <= 10), SIMATIC S7-200 SMART CPU SR60 (6ES7 288-1SR60-0AA0) (All versions <= V2.5.0 and Function State (FS) <= 12), SIMATIC S7-200 SMART CPU ST20 (6ES7 288-1ST20-0AA0) (All versions <= V2.5.0 and Function State (FS) <= 9), SIMATIC S7-200 SMART CPU ST30 (6ES7 288-1ST30-0AA0) (All versions <= V2.5.0 and Function State (FS) <= 9), SIMATIC S7-200 SMART CPU ST40 (6ES7 288-1ST40-0AA0) (All versions <= V2.5.0 and Function State (FS) <= 8), SIMATIC S7-200 SMART CPU ST60 (6ES7 288-1ST60-0AA0) (All versions <= V2.5.0 and Function State (FS) <= 8), SIMATIC S7-200 SMART CPU family (All versions). There is an access mode used during manufacturing of the affected devices that allows additional diagnostic functionality. The security vulnerability could be exploited by an attacker with physical access to the UART interface during boot process. |