Search Results (2290 CVEs found)

CVE Vendors Products Updated CVSS v3.1
CVE-2016-7959 1 Siemens 1 Simatic Step 7 2025-04-12 N/A
Siemens SIMATIC STEP 7 (TIA Portal) before 14 improperly stores pre-shared key data in TIA project files, which makes it easier for local users to obtain sensitive information by leveraging access to a file and conducting a brute-force attack.
CVE-2015-4174 1 Siemens 1 Climatix Bacnet\/ip 2025-04-12 N/A
Cross-site scripting (XSS) vulnerability in the integrated web server on the Siemens Climatix BACnet/IP communication module with firmware before 10.34 allows remote attackers to inject arbitrary web script or HTML via a crafted URL.
CVE-2015-1602 1 Siemens 1 Simatic Step 7 2025-04-12 N/A
Siemens SIMATIC STEP 7 (TIA Portal) 12 and 13 before 13 SP1 Upd1 improperly stores password data within project files, which makes it easier for local users to determine cleartext (1) protection-level passwords or (2) web-server passwords by leveraging the ability to read these files.
CVE-2015-1601 1 Siemens 1 Simatic Step 7 2025-04-12 N/A
Siemens SIMATIC STEP 7 (TIA Portal) 12 and 13 before 13 SP1 Upd1 allows man-in-the-middle attackers to obtain sensitive information or modify transmitted data via unspecified vectors.
CVE-2016-4785 1 Siemens 9 Siprotec 4 En100, Siprotec Compact Model, Siprotec Compact Model 7rw80 and 6 more 2025-04-12 N/A
A vulnerability has been identified in Firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All versions < V1.11.00; Firmware variant DNP3 TCP for EN100 Ethernet module : All versions < V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions < V1.21; EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions < 1.02.02. The integrated web server (port 80/tcp) of the affected devices could allow remote attackers to obtain a limited amount of device memory content if network access was obtained. This vulnerability only affects EN100 Ethernet module included in SIPROTEC4 and SIPROTEC Compact devices.
CVE-2015-1599 1 Siemens 1 Spcanywhere 2025-04-12 N/A
The Siemens SPCanywhere application for iOS allows physically proximate attackers to bypass intended access restrictions by leveraging a filesystem architectural error.
CVE-2015-1597 1 Siemens 1 Spcanywhere 2025-04-12 N/A
The Siemens SPCanywhere application for Android does not use encryption during the loading of code, which allows man-in-the-middle attackers to execute arbitrary code by modifying the client-server data stream.
CVE-2015-1596 1 Siemens 1 Spcanywhere 2025-04-12 N/A
The Siemens SPCanywhere application for Android and iOS does not properly verify X.509 certificates from SSL servers, which allows man-in-the-middle attackers to spoof servers and obtain sensitive information via a crafted certificate.
CVE-2016-2846 1 Siemens 2 Simatic S7 1200 Cpu, Simatic S7 Cpu 1200 Firmware 2025-04-12 N/A
Siemens SIMATIC S7-1200 CPU devices before 4.0 allow remote attackers to bypass a "user program block" protection mechanism via unspecified vectors.
CVE-2015-1355 1 Siemens 1 Simatic Step 7 2025-04-12 N/A
Siemens SIMATIC STEP 7 (TIA Portal) before 13 SP1 uses a weak password-hash algorithm, which makes it easier for local users to determine cleartext passwords by reading a project file and conducting a brute-force attack.
CVE-2015-5717 1 Siemens 1 Compas 2025-04-12 N/A
The Siemens COMPAS Mobile application before 1.6 for Android does not properly verify X.509 certificates from SSL servers, which allows man-in-the-middle attackers to spoof servers and obtain sensitive information via a crafted certificate.
CVE-2015-5698 1 Siemens 2 Simatic S7 1200 Cpu, Simatic S7 1200 Cpu Firmware 2025-04-12 N/A
Cross-site request forgery (CSRF) vulnerability in the web server on Siemens SIMATIC S7-1200 CPU devices with firmware before 4.1.3 allows remote attackers to hijack the authentication of unspecified victims via unknown vectors.
CVE-2014-2255 1 Siemens 1 Simatic S7-1500 Cpu Firmware 2025-04-12 N/A
Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 allow remote attackers to cause a denial of service (defect-mode transition) via crafted HTTP packets.
CVE-2014-2909 1 Siemens 6 Simatic S7 Cpu-1211c, Simatic S7 Cpu 1200 Firmware, Simatic S7 Cpu 1212c and 3 more 2025-04-12 N/A
CRLF injection vulnerability in the integrated web server on Siemens SIMATIC S7-1200 CPU devices 2.x and 3.x allows remote attackers to inject arbitrary HTTP headers via unspecified vectors.
CVE-2015-1595 1 Siemens 1 Spcanywhere 2025-04-12 N/A
The Siemens SPCanywhere application for Android and iOS does not use encryption during lookups of system ID to IP address mappings, which allows man-in-the-middle attackers to discover alarm IP addresses and spoof servers by intercepting the client-server data stream.
CVE-2014-9369 1 Siemens 6 Spc4000, Spc4000 Firmware, Spc5000 and 3 more 2025-04-12 N/A
Siemens SPC controllers SPC4000, SPC5000, and SPC6000 before 3.6.0 allow remote attackers to cause a denial of service (device restart) via crafted packets.
CVE-2014-2251 1 Siemens 1 Simatic S7-1500 Cpu Firmware 2025-04-12 N/A
The random-number generator on Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 does not have sufficient entropy, which makes it easier for remote attackers to defeat cryptographic protection mechanisms and hijack sessions via unspecified vectors.
CVE-2014-2249 1 Siemens 1 Simatic S7-1500 Cpu Firmware 2025-04-12 N/A
Cross-site request forgery (CSRF) vulnerability on Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 and SIMATIC S7-1200 CPU PLC devices with firmware before 4.0 allows remote attackers to hijack the authentication of unspecified victims via unknown vectors.
CVE-2016-9160 1 Siemens 2 Simatic Pcs 7, Simatic Wincc 2025-04-12 N/A
A vulnerability in SIEMENS SIMATIC WinCC (All versions < SIMATIC WinCC V7.2) and SIEMENS SIMATIC PCS 7 (All versions < SIMATIC PCS 7 V8.0 SP1) could allow a remote attacker to crash an ActiveX component or leak parts of the application memory if a user is tricked into clicking on a malicious link under certain conditions.
CVE-2014-2247 1 Siemens 1 Simatic S7-1500 Cpu Firmware 2025-04-12 N/A
The integrated web server on Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 allows remote attackers to inject headers via unspecified vectors.